WNS Fuel type: Diesel oil, heavy oil, natural gas, city gas Boiler character: Use ripple furnace and screw thread smoke tube, high heat efficiency; Horizontal three-pass and wet back structure; Automatic control system Remark: The burner brand is according to the order of user
|
WNS0.7-0.7 -95-70-Y(Q) |
WNS1.4-0.7 -95-70-Y(Q) |
WNS2.1-0.7 -95-70-Y(Q) |
WNS2.8-0.7 -95-70-Y(Q) |
WNS3.5-0.7 -95-70 |
WNS4.2-0.7 -115-70 |
WNS5.6-0.7 -115-70 |
WNS7.0-0.7 -115-70 |
(MW) thermal power |
0.7 |
1.4 |
2.1 |
2.8 |
3.5 |
4.2 |
5.6 |
7.0 |
(MPa) Working pressure |
0.7 |
0.7 |
0.7 |
0.7 |
1.0 |
1.0 |
1.0 |
1.0 |
(C) Outlet water temperature |
95 |
95 |
95 |
95 |
95 |
115 |
115 |
115 |
(C) return water temperature |
70 |
70 |
70 |
70 |
70 |
70 |
70 |
70 |
(t/h) Quantily of circulating water |
24 |
48 |
72 |
96 |
120 |
80 |
107 |
133 |
(%) Efficiency |
92.48 |
92.08 |
90.08 |
91.04 |
91.4 |
91.1 |
91.4 |
90 |
Fuels suitable |
\\\ Light oil,Heavy oil,Natural gas,Liquefied gas |
(kg/h) the boiler full load Light oil consumption |
61.95 |
128.6 |
192.68 |
257.8 |
327 |
39 |
524 |
658 |
(Nm³/h) the boiler full load Natural gas consumption |
71.5 |
148.3 |
223.1 |
297.6 |
374.4 |
450.5 |
601.5 |
754.8 |
(kJ/h) the boiler full load Heavy oil consumption |
66.8 |
137.5 |
207.1 |
275.6 |
343.9 |
41.3 |
554.4 |
692.7 |
Large transport size |
3.18×1.37×1.89 |
3.97×1.50×2.17 |
4.76×2.59×2.64 |
5.12×2.68×2.88 |
5.66×2.41×3.17 |
6.3×2.56×3.17 |
6.94×2.62×3.32 |
7.0×2.76×3.48 |
Max transport weight |
3.33 |
4.838 |
6.849 |
8.9 |
15.6 |
17.8 |
21.2 |
26.4 |
Applicable altitude |
1000 |
LD. Of supply water |
DN80 |
DN100 |
DN125 |
DN125 |
DN125 |
DN150 |
DN150 |
DN150 |
LD. Of outlet water |
DN80 |
DN100 |
DN125 |
DN125 |
DN125 |
DN150 |
DN150 |
DN150 |
LD. Of safety valve |
DN40 |
DN40 |
DN50 |
DN50 |
DN80 |
DN80 |
DN100 |
DN100 |
LD. Of blow down pipe |
DN40 |
DN40 |
DN40 |
DN40 |
DN50 |
DN50 |
DN50 |
DN50 |
chimney diameter |
350 |
350 |
450 |
450 |
500 |
500 |
700 |
700 |